Difference between revisions of "Batteries"
***** (***** | *****) |
***** (***** | *****) |
||
Line 20: | Line 20: | ||
= Selection of Battery Technology<br/> = | = Selection of Battery Technology<br/> = | ||
− | The selection of the appropriate battery technology according to the requirements is a crucial part of the design of a system. These requirements may differ by project region. <br/> | + | The selection of the appropriate battery technology according to the requirements is a crucial part of the design of a system. These requirements may differ by project region.<br/> |
Below a selection of considerations can be found. A weighting, as mentioned, depends on the installed system type and various specific factor of the project country (e.g. knowledge of technology, maintenance structure,...).<br/> | Below a selection of considerations can be found. A weighting, as mentioned, depends on the installed system type and various specific factor of the project country (e.g. knowledge of technology, maintenance structure,...).<br/> | ||
Line 498: | Line 498: | ||
== Nickel Iron Batteries == | == Nickel Iron Batteries == | ||
<div class="mw-collapsible mw-collapsed"> | <div class="mw-collapsible mw-collapsed"> | ||
− | The '''nickel iron battery (NiFe battery)''' is a storage battery having a nickel(III) oxide-hydroxide cathode and an iron anode, with an electrolyte of potassium hydroxide. The active materials are held in nickel-plated steel tubes or perforated pockets. The nominal cell voltage is 1.2V. It is a very robust battery which is tolerant of abuse, (over charge, over discharge, short-circuiting and thermal shock) and can have very long life even if so treated. It is often used in backup situations where it can be continuously charged and can last for more than 20 years. | + | The '''nickel iron battery (NiFe battery)''' is a storage battery having a nickel(III) oxide-hydroxide cathode and an iron anode, with an electrolyte of potassium hydroxide. The active materials are held in nickel-plated steel tubes or perforated pockets. The nominal cell voltage is 1.2V. It is a very robust battery which is tolerant of abuse, (over charge, over discharge, short-circuiting and thermal shock) and can have very long life even if so treated. It is often used in backup situations where it can be continuously charged and can last for more than 20 years.It also has a high temperature resistance with an operating window between -40 and +46 degree Celsius. |
One major difference between nickel iron and Ni Cad batteries is discharge rate. Nickel iron batteries cannot deliver the extremely high currents that Ni Cad batteries can, so if heavy loads are used, a larger capacity battery bank has to be employed. | One major difference between nickel iron and Ni Cad batteries is discharge rate. Nickel iron batteries cannot deliver the extremely high currents that Ni Cad batteries can, so if heavy loads are used, a larger capacity battery bank has to be employed. | ||
Line 683: | Line 683: | ||
<br/> | <br/> | ||
+ | [[Category:Solar_Home_Systems_(SHS)]] | ||
+ | [[Category:Solar]] | ||
[[Category:Battery_Charging_Systems]] | [[Category:Battery_Charging_Systems]] | ||
− | |||
− |
Revision as of 05:15, 11 August 2017
Overview
Most of the information at this wiki page on batteries for solar systems is taken from: Polar Power Inc., except for the paragraphs on nickel iron batteries and recycling and otherwise indicated paragraphs.
Batteries store the electrical energy generated by the modules during sunny periods, and deliver it whenever the modules cannot supply power. Normally, batteries are discharged during the night or cloudy weather. But if the load exceeds the array output during the day, the batteries can supplement the energy supplied by the modules.
The interval which includes one period of charging and one of discharging is described as a "cycle." Ideally, the batteries are recharged to 100 % capacity during the charging phase of each cycle. The batteries must not be completely discharged during each cycle.
No single component in a photovoltaic (PV) system is more affected by the size and usage of the load than storage batteries. If a charge controller is not included in the system, oversized loads or excessive use can drain the batteries' charge to the point where they are damaged and must be replaced. If a controller does not stop overcharging, the batteries can be damaged during times of low or no load usage or long periods of full sun.
For these reasons, battery systems must be sized to match the load. In addition, different types and brands of batteries have different "voltage set point windows." This refers to the range of voltage the battery has available between a fully discharged and fully charged state.
As an example, a battery may have a voltage of 14 volts when fully charged, and 11 when fully discharged. Assume the load will not operate properly below 12 volts. Therefore, there will be times when this battery cannot supply enough voltage for the load. The battery's voltage window does not match that of the load.
Selection of Battery Technology
The selection of the appropriate battery technology according to the requirements is a crucial part of the design of a system. These requirements may differ by project region.
Below a selection of considerations can be found. A weighting, as mentioned, depends on the installed system type and various specific factor of the project country (e.g. knowledge of technology, maintenance structure,...).
Storage Technology Requirements[1]:
- Availability
- Local Knowledge of Technique
- Complexity
- Durability
- Scalability
- Environment/ Health Impact
- Costs
- Vulnerability
- Establishment
- Manufacturability
- Maintenance
A radar-diagram (or spider web) can help to visualise these specific requirements.
Performance
The performance of storage batteries is described in two ways:
- amp-hour capacity
- depth of cycling
Amp-hour Capacity
Charge and Discharge Rates
Temperature
Depth of Discharge (DOD)
Different Battery Types
Batteries can be classified in 2 categories.
Primary Batteries
Secondary Batteries
Lead Acid Batteries
Vented Lead Acid Batteries
Internal Construction
Terminals
Venting
State of Charge, Specific Gravity and Voltage
Freezing Point
Sealed Flooded (Wet) Lead Acid Batteries
Captive Electrolyte Batteries
Nickel Cadmium (Ni Cad) Batteries
Nickel Iron Batteries
Lithium Ion Batteries
Ice Bear
lithium-air
Chosing a Battery for a Solar Home System (SHS)
Typical Problems of Batteries
Sulfation
Treeing
Mossing
Recycling of Batteries of Photovoltaic (PV) Systems
Further Information
References